Consumer Unit Replacement
Purpose
This document covers the procedure for replacing a domestic consumer unit (fuseboard). Consumer unit replacement is a notifiable job under Part P — it must be self-certified via our competent person scheme.
When Is a Consumer Unit Replacement Needed?
- Old fusebox with rewirable fuses — no RCD protection, does not meet modern standards
- Nuisance tripping on a split-load board — full RCBO board gives each circuit independent protection
- Insufficient circuits for new additions (EV charger, heat pump, etc.)
- Consumer unit damaged or failed
- Landlord requiring compliance before letting
Before Starting — Survey and Quote
Establish:
- Supply size: What is the main fuse / cut-out rating? (Typically 60A, 80A, or 100A for domestic)
- Number of circuits: How many circuits are present? The new board must accommodate all of them plus spare ways.
- Earthing arrangement: TN-S, TN-C-S/PME, or TT? This affects the type of SPD required.
- Meter tails condition: Are the tails in good condition? If they need replacing, quote accordingly.
- Existing installation condition: A consumer unit replacement on deteriorating wiring requires an EICR to confirm the existing installation is satisfactory.
Materials
- Consumer unit: Correct number of ways + 2–4 spare. Metal or metal-lined enclosure (BS EN 61439-3). Hager, Schneider, Wylex, Crabtree.
- RCBOs: One per circuit — rated to match the circuit (6A lighting, 32A ring, 40–45A cooker/shower)
- Meter tails: 25mm² — buy more than needed
- Earth cable: 16mm² green/yellow
- SPD (Surge Protection Device): Type 2 SPD required for TN-C-S (PME) earthing under 18th Edition Amendment 2
- Cable clips, trunking for meter tail protection
Procedure
Step 1 — Notify via Competent Person Scheme
Register the job before starting, or ensure notification is completed on the day.
Step 2 — Isolate and Test Dead
Switch off the consumer unit main switch. Test that all circuits are dead using a voltage indicator before working — do not assume.
Wilsons cannot isolate the supply side of the meter. If the meter tails must be disconnected, contact the DNO for a temporary disconnection.
Step 3 — Label All Circuits
Before disconnecting anything, label every circuit cable. Take a photograph of the existing board wiring for reference.
Step 4 — Disconnect the Old Board
- Switch off the main switch
- Disconnect each circuit cable — label as you go
- Disconnect the earthing and bonding conductors
- Disconnect the meter tails at the main switch
- Remove the old consumer unit
Step 5 — Prepare and Fix New Consumer Unit
- Fix the back box to the wall — confirm level and that meter tails will reach
- Install consumer unit body
- Install RCBOs in correct positions (larger loads near the main switch for shorter internal runs)
- Fit the SPD as specified in the consumer unit instructions
Step 6 — Connect the Incoming Supply
- Meter tails → main switch: Brown/red (L) and Blue/black (N)
- Earthing conductor → earth bar
- Main bonding conductors (gas and water) → earth bar
Meter tails must be protected where exposed — use trunking or conduit.
Step 7 — Connect the Circuits
For each circuit:
- Live (brown/red) → RCBO input terminal
- Neutral (blue/black) → neutral bar
- Earth (green/yellow) → earth bar
Tighten all terminals to the manufacturer's torque specification — loose terminals are a fire risk.
Step 8 — Pre-Energisation Tests
Before switching on:
Continuity of earth conductors: Test continuity from each circuit earth back to the earth bar.
Polarity: Confirm live and neutral are not reversed on each circuit.
Insulation resistance: With all RCBOs off and main switch off, test L-E, N-E on each circuit. Minimum: 1 MΩ. Disconnect LED drivers and sensitive electronics before testing.
Record all readings.
Step 9 — Energise and Final Tests
- Switch on main switch
- Switch on each RCBO — confirm each circuit comes on without tripping
- Confirm each circuit supplies the correct area
- Test each RCBO with the test button — confirm trip and reset
- RCD trip time test using MFT — record results
- Confirm SPD indicator shows healthy
Step 10 — Documentation
Electrical Installation Certificate (EIC): Required for a new consumer unit. Complete all sections including test results.
Notify via NICEIC to self-certify and generate the Building Regulations compliance certificate.
Leave with customer: Copy of EIC, consumer unit operating manual, instructions for resetting RCBOs.
Common Issues
| Problem | Fix |
|---|---|
| RCBO trips immediately on energising circuit | Fault on that circuit — do not leave on; investigate |
| Insulation resistance below 1MΩ | Fault in circuit wiring — locate and repair before energising |
| Neutral bar overcrowded | Use double-entry terminal or additional neutral bar |
| Meter tails won't reach new board position | Extend with same cable size (25mm²) and correct connector, or reposition board |
| SPD alarm light on | SPD has operated — check if replacement needed |
