Wilsons Systems
· ·
v · · Reviewed by

Annual Service & Inspection — Fire Alarms

Purpose

This document covers the fire alarm annual service and inspection procedure. Fire alarms are legally required to be maintained to BS 5839-1 — regular inspection and testing by a competent engineer is mandatory.


Legal and Standards Requirement

Under the Regulatory Reform (Fire Safety) Order 2005, the responsible person for any non-domestic premises must ensure fire detection and alarm systems are maintained in efficient working order.

BS 5839-1 maintenance requirements:

  • Weekly: Test at least one manual call point (rotated around all MCPs)
  • 6-monthly: Full inspection and test by a competent engineer
  • Annually: Full service including battery test, detector test, and documentation updated

Before the Visit

  1. Notify the customer — agree a time when the alarm can be tested without causing concern to occupants
  2. Notify the ARC — if the system signals to a monitoring centre, inform them testing is taking place so they do not dispatch the fire brigade
  3. Review the logbook — check for outstanding actions or deferrals from the previous visit

The Service Checklist

Panel Inspection

  • Panel in normal condition — no faults or alerts displayed
  • Panel clean — no dust, moisture, or debris inside
  • Date and time correct on panel clock
  • Event log reviewed — note any significant events since last service
  • Access code confirmed working (engineer level)

Mains Power

  • Mains supply present and panel showing mains healthy
  • Fuse/MCB correct rating and accessible
  • Mains cable condition — no visible damage

Standby Battery

  • Battery condition — no swelling, leakage, or damage
  • Battery age confirmed — note manufacture date. Replace if older than 4 years or if load test fails.
  • Battery load test — remove mains supply; confirm panel operates correctly from battery. Restore mains after test.

Detection Devices — Visual Inspection

  • Detectors clean — no dust, paint, or obstructions on sensing chamber
  • Detectors secure — heads firmly seated in bases, bases fixed to ceiling
  • No unauthorised repositioning by the customer
  • No physical damage to any device

Detection Devices — Functional Test

BS 5839-1 requires all detectors to be tested at least annually. On the annual visit, all detectors must be tested.

Smoke detectors: Apply approved smoke aerosol (e.g. Hochiki KI-1 or equivalent approved test spray). Confirm the panel registers the correct device. Reset before moving to next.

Heat detectors: Use an approved heat detector test tool (hot air blower designed for detector testing — not a naked flame or lighter). Confirm the panel registers the correct device.

Manual Call Points — Functional Test

All MCPs must be tested at least annually.

  • Use the test key to activate each MCP (do not break the glass element on a routine test)
  • Confirm the panel registers the correct MCP in alarm
  • Reset each MCP with the test key after testing
  • Replace any broken glass elements

Sounders and Beacons — Functional Test

  • Activate all sounders via the panel test function
  • Walk all areas — confirm sounders are audible throughout the protected area
  • Confirm all beacons/strobes flash when activated

Remote Signalling (ARC) — Test

  • Inform the ARC a test signal is being sent
  • Send a test signal from the panel
  • Confirm the ARC received the signal
  • Inform the ARC that testing is complete

Cabling and Wiring Visual Check

  • Cable condition where visible — clips secure, no damage
  • Wiring at the panel — no loose connections, no corrosion
  • Junction boxes — covers in place, wiring secure

After Testing

  1. Reset all faults and test modes — ensure the panel is back in normal condition
  2. Restore ARC monitoring — confirm with the ARC
  3. Complete the service report
  4. Update and sign the logbook on site
  5. Report deficiencies to the customer verbally and in writing

Service Report — What It Must Include

The service report is a legal document:

  • Site name, address, and system reference
  • Date of service
  • Engineer name and company
  • Panel type and serial number
  • All items tested and their results (pass/fail)
  • Battery age and condition
  • Any deficiencies identified
  • Any recommendations or required actions
  • Engineer signature

The customer must receive a copy. File a copy in Simpro.


Common Deficiencies Found on Service Visits

DeficiencyAction
Battery older than 4 yearsReplace — quote if not on site stock
Detector painted overReplace immediately — paint blocks sensing chamber
Detector covered by stored itemsAdvise customer to clear space
Sounders not audible in part of buildingAssess and document — additional sounder may be needed
Customer added partition blocking detectorRe-survey and quote additional coverage
Call point glass brokenReplace glass element
No logbook on siteProvide a new logbook and complete it

Related Documents

/ / Fire Alarms · v · · Wilsons Systems