Videx 4000 Series Video Entry — Fault Finding

Written after a three-visit job on a three-flat block where a simple "no release" fault turned into a mechanical lock problem. Read this before starting on any Videx 4000 series video entry system.

System on this job

ItemPartNotes
Entrance panelVidex 4384X-0 (steel)Button modules fitted behind the panel
Video distributionVidex ART.317N2-flat unit
Bus power supplyVidex ART.2321Switching PSU, 32V DC, 0.8A. Powers the intercom bus only
Lock power supplyMean Well HDR-15-1212V DC, 1.25A. Powers the door lock only
HandsetsVidex colour video monitors with handsetOne per flat
Button moduleSN4320 (original), replaced with Videx 4043/M3-button module

Two separate power supplies. The 32V bus PSU and the 12V lock PSU are independent. A dead lock PSU gives "door won't release" while calls and video still work fine. Test the two supplies separately before you touch anything else.


Fault 1 — Door will not release, but calls and video work

  1. Measure the 12V lock PSU output with a meter. On this job the Mean Well PSU had no output. That was the original fault.

  2. If the PSU is dead, replace it with a like-for-like 12V DC unit.

  3. Check the lock wiring polarity before powering up. On this lock the correct connections were:

    • Brown / White-Brown = positive
    • Green / White-Green = negative

    The previous contractor had reconnected them in reverse. Check the polarity of the lock you are on. Do not assume the same colours apply to every lock.

  4. Test release from each flat's handset.


Fault 2 — One button on the panel doesn't call its flat

Symptom: Button 1 would not call Flat 151, but the other buttons worked.

Diagnosis by swap test (do this before ordering anything):

  1. Swap the handset with one known to work. If the fault stays with the button, the handset is fine.
  2. Swap the call button assignments on the panel. If the fault follows the button position, the button module is faulty, not the handset or the wiring.
  3. Here the cause was an intermittent micro switch on the SN4320 button module.

Temporary fix if the replacement part isn't on the van: swap the button assignments so the faulty position is not used for an occupied flat. Restores service immediately while you order the part.

Permanent fix: replace the module with a Videx 4043 (3-button) module. All three buttons worked within about 20 minutes of fitting.

Finish matching: the module fitted was the matte 4043/M, while the panel is steel. It works, but the finish doesn't match. If a like-for-like finish is needed, order the polished steel 4043 up front. Confirm the finish with the customer before fitting.


Lesson — Don't get drawn into the door's mechanical lock

On arrival the door's lock mechanism had been completely dismantled by a previous contractor, with mounting bolts missing. We restored the electric release using temporary bolts from van stock, then returned to fit the correct ones.

During that later visit, the internal sliding bar linking the electric release to the mechanical multipoint lock was dislodged. The bar snagged on a fixing plate when the handle was operated. The top bolt jammed with no manual override, and a small clearance cut had to be made to free it. A locksmith was then needed for the mechanical side.

Rules for next time:

  • Photograph the lock and door as found, before touching anything, and record anything already missing or damaged.
  • We only work on the electric (solenoid) side. The mechanical multipoint lock is a locksmith or door-fitter job.
  • Put that limit in writing on the quote and tell the customer before starting.
  • Do not refit or tension mechanical parts "to get the electric release working" without agreement. If the mechanism is dismantled on arrival, stop, record it and tell the customer.
  • Don't leave the building with only one way out. Before you disturb any lock, check that the doors have a working means of escape. If the lock is stuck or jammed, the occupants may be unable to leave.

Fire safety observation

The building had a single exit with no secondary means of escape. Any mechanical lock failure therefore leaves residents without a viable way out. If you find this on any site, raise it in writing with the building owner or freeholder.


Quick reference

SymptomCheck firstLikely fix
No door release, calls OK12V lock PSU outputReplace PSU, check lock polarity
No calls, no video anywhere32V ART.2321 bus PSUCheck 32V output and bus wiring
One button doesn't callSwap handset, then swap button assignmentsReplace button module (4043)
Handset works, button intermittentMicro switch on the button moduleReplace module
Release clicks but door won't openMechanical lock / multipointLocksmith. Outside our scope