Getting Started: Inspection & Testing
Purpose
This section is a practical reference for inspecting and testing low voltage electrical installations: new work, alterations and additions, and periodic inspection. It explains the order of the tests, how to carry each one out, what a normal reading looks like, and how to isolate safely before you start.
It supports the standards. It does not replace them.
The Standards That Govern It
- BS 7671 (the Wiring Regulations), Part 6, sets out the inspection and testing requirements and the acceptable results.
- IET Guidance Note 3 (GN3) explains how to carry out each test and in what order.
- IET On-Site Guide gives the tables most often needed on site, including expected R1+R2 values.
- Electricity at Work Regulations 1989 and HSE GS 38 cover safe working and test equipment.
Always work from the current editions.
Habits That Keep Results Reliable
- Inspect before you test. A visual inspection comes first.
- Isolate safely every time. See Safe Isolation.
- Use approved test equipment. Check it is in date and undamaged. Null the test leads before continuity tests. Record the tester serial number and calibration date.
- Work in the right order. Dead tests first, then live tests. See Sequence of Tests.
- Write results down as you test. Fill in the Schedule of Test Results as each test is done, not from memory afterwards.
- Check every reading. Compare it with what you expect and with the limits in BS 7671 before moving on. See Expected Readings.
- Put everything back. Anything disconnected for a test must be reconnected and tight before the supply is restored.
Where to Go Next
- Safe Isolation: the basic procedure and the 10 tests for proving dead
- Sequence of Tests: dead tests then live tests, step by step
- Ring Final Circuit Test: the three-step test and what each reading means
- Expected Readings: R1+R2 and bonding values, and how they lead to Zs